A known damage mechanism in industry is identified as "Crevice Corrosion". A concentration of corrosive materials or combinations of substance to form an aggressive corrosion solution in which is located at a specific point to accelerate damage is known crevice corrosion.
An example of this damage mechanism is the corrosion that occurs between seals on two opposing flanges with a gasket placed in-between the seals.
Concentrations of corrosive materials collect within a crevice such as between sealing surfaces and gasket material. Because of the concentration of the corrosive material in a localized area the rate of corrosion is accelerated. Corroding or loss of sealing area can cause loss of containment therefore potential for catastrophic release with loss of assets, production and injury to personnel.

Cross Sectional View of Raised Face Flange
Testing the sealing surface of flanges has become a standard practice. This test is performed in-situ as part of a run and maintain program. Testing is also common as a pre-turnaround exercise to determine which flanges need to be repaired.
Field machining of the flange face is performed as an in-situ repair. This testing technique can determine if the flange face has been machined and if loss of sealing area occurred. In the situation where there is no more seal to repair then the flange must be replaced or possibly the seal area will be renewed using a weld build up technique.
Caution: If the flange face has been repaired by welding and machining then UT inspection might detect this weld as an interface. As the interface is detected this signal can be confused as loss of sealing area.
The two most common positions for placing the UT transducers are on the flange taper and between the bolt holes. As illustrated in the photographs below.
Taper areas of flanges are not always the same therefore geometry must be plotted for each flange. This step is difficult and can lead to error in condition assessment.

This technique is performed by placing the phased array transducer on the angled section of the flange.
Due to design requirements and normal manufacturing process the location between the bolt holes is square to the flange face. This location is also consistent in distance therefore repeated applications can be compared. In some cases two bolts must be removed at each quadrant for the UT probe to fit properly. Removing the bolts is only done if the flange is offline and depressurized. If highly hazardous materials are contained by the subject flange then removal of bolts may not be allowed.

With this technique the phased array transducer is applied between the bolts.
These photos are an example of raised face flanges as applicable to piping.

Phased Array Transducer can be placed on the angled section of the flange

Phased Array Transducer can be placed between the bolt holes
Using the ES Beam Tool can help perform a setup phased array techniques

Phased array applied with the transducer on the flange taper.

Phased array applied with the transducer between the bolt holes.
The primary focus for this application are manufacturers and/or users of Hydrofluoric Acid (HF). HF units are common in refineries and chemical plants. Other types of processes can attack the flange seal location including acids, steam and salt water.
A calibration standard should be used to confirm the phased array setup. Using a duplicate of the flange size and weight with targets manufactured in the raised face sealing area for UT performance demonstration is the ultimate confirmation of setup performance.
Example of calibration standard:

A = .075 in. deep X 1.0" long
B = .050 in. deep X 1.0" long
C = .025 in. deep X 1.0" long

Examination of raised face flanges can be performed using the Epoch 1000, Omniscan MXU-M or Omniscan MX.
Our small Phased Array Probes are well suited for flanges with smaller distances between the bolts and nuts.
Industry has used single channel flaw detectors such as the Epoch XT with good success. The test is concluded with only numerical values illustrating loss of sealing area. No image is provided therefore only the inspectors word is left in writing.
El EPOCH 1000 es un detector de defectos por ultrasonidos convencional de avanzada al que se puede optimizar adicionando la creación de imágenes phased array en un centro de servicio autorizado de Olympus. Sus características claves son: la conformidad a norma EN12668-1, un juego de 37 filtros digitales en el receptor y una frecuencia de repetición de impulsos de 6 kHz para la inspección a alta velocidad.
El EPOCH XT es un detector de defectos por ultrasonidos portátil de avanzada, que cuenta con numerosas funciones estándares de medición, incluyendo un emisor de ondas cuadradas ajustable, filtros digitales de banda estrecha y de banda ancha seleccionables, una gama de ganancias de 0 a 110 dB, las funciones de memoria y de mantenimiento de picos y una frecuencia de repetición de impulsos (PRF) ajustable.
El OmniScan MX es un detector de defectos de punta que integra múltiples tecnologías. Ofrece una alta velocidad de adquisición y potentes funciones software incorporadas en un instrumento portátil y modular, que permite realizar inspecciones manuales y automatizadas eficaces. Disponible con los módulos de ultrasonidos convencional y phased array (PA) así como con los módulos de corrientes de Foucault (EC) convencional y multielementos (ECA).
El módulo OmniScan MXU-M es la solución accesible que ofrece las ventajas de la creación de imágenes phased array durante las inspecciones manuales, además de todas las ventajas de un producto ya probado. Entre sus funciones se encuentran: los módulos phased array de base (serie M), la detección de defectos en las inspecciones por ultrasonido manuales y la creación de imágenes phased array en tiempo real.Copyright 2011 OLYMPUS CORPORATION, todos los derechos reservados. Condiciones de uso | Política de privacidad